except when the device is being viewed, in which case it is
updated once per minute.
FldType: Field Type: The device type as seen by the fire panel. *See
Page 80 for field type descriptions.
FldDt: The value returned by a manual call point is one of three:
16 - Fault
32 - Normal
128 - Fire Alarm
The protocol being used to communicate to this device is also
displayed. They are: ARI - Aritech Series 2000
X90 - Aritech Series 900
X95 - Aritech Series 950
TestVal: The value returned during Device Self-Test. A value that is less
than the alarm threshold will result in a maintenance condition.
Alarms: The number of fire alarms produced by the device since the last
clear statistics operation.