EasyManua.ls Logo

Arjo Tornado - Page 74

Arjo Tornado
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74
6.5.2.1 Cleaning the steam generator
If the water is hard (above about 6 dH) there is a risk of limescale
deposits forming on the elements of the steam generator. The
elements should be checked and cleaned once or twice a year.
Remove the cover below the ball valve. Empty the steam
generator by opening the ball valve.
Remove the hose and the check valve.
Remove the entire steam generator from the pipe system of
the machine. Before the steam generator can be opened, the
insulation must be removed and then the clamping ring.
Remove any limescale deposits on the elements with
limescale remover or mechanically (take care, since the
elements are welded to the end panel).
Before re-assembling the steam generator, replace the O-ring
EHWZHHQWKHKDOYHVRIWKHWDQN7KHQ¿WWKHFODPSLQJULQJ
Tighten carefully to avoid damaging the O-ring.
5H¿WWKHLQVXODWLRQDQGVHFXUHLWZLWKDGKHVLYHWDSH
Fit the cover to the ball valve, making sure that the ball valve
is closed.
Install the steam generator on the pipe system. The gasket
between the steam generator and the pipe system of the
machine must be replaced.
5H¿WWKHKRVHDQGQRQUHWXUQYDOYH
If there is leakage from the check valve, dismantle the check
valve and clean the sealing surfaces in the valve body and
on the O-ring. On re-assembly, the locking screw must be
screwed in until it bottoms in the valve body.
If the problem with the deposits is severe, we recommend
LQFUHDVLQJWKHGRVDJHDPRXQWVHH³&KHFNLQJWKHGRVDJH
amount”).
1
2
7
6
8
3
4
5
001440
Figure 8. Components in the steam generator
1. Check valve 5. Cover
2. Sealing 6. O-ring
3. Overheat protection 7. Clamping ring
4. Ball valve 8. Insulation

Table of Contents

Other manuals for Arjo Tornado

Related product manuals