6. Power Consumption
6.1 Mains Power
6.1.1 BPS-405
The current consumption at 115V AC is 3,2A.
The current consumption at 230V AC is 1,6A.
The inrush peak current consumption is 35A.
6.1.2 BPS-410
The current consumption at 115V AC is 4,5A.
The current consumption at 230V AC is 1,9A.
The inrush peak current consumption is 35A.
6.2 System Units
System Unit
Current Consumption
Fire Alarm Control Panel BS-420
Controller BC-420
156mA/27V DC (idle)
Max. 340mA/27V DC
Repeater Panel BU-BV-420
156mA/22,2V DC (idle)
Max. 220mA/27V DC (lamp test)
Operator Panel BS-430
175mA/27V DC (idle)
Max. 340mA/27V DC (lamp test)
Power Board BSF-400
85mA
6.3 Loop Units
For information on the current consumption for various loop units,
refer to technical specifications provided in the relevant datasheets.