Appendix B - Power Supply
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. I, 2014-04-01,
Autronica Fire and Security AS
Page 82
15.9 Dipswitch table – S5 and S6
Dipswitch table S5
S5.1
S5.2
Function
OFF
OFF
AutroFieldBus earth fault OFF
ON
ON
AutroFieldBus earth fault ON
Dipswitch table S6
Switch
Name
Comment
S6.1
Earth Fault
ON: Earth fault monitoring
activated
OFF: Earth fault monitoring
deactivated
S6.2
--
NA
S6.3
AutroFieldBus
ON: AutroFieldBus connected
OFF: AutroFieldBus not
connected
S6.4
Not used
NA
S6.5
Battery
ON: Battery connected
OFF: Battery not connected
S6.6
Power Unit Type
ON: BPS-405
OFF: BPS-410