Service and Maintenance
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. I, 2014-04-01,
Autronica Fire and Security AS
Page 61
Step
Description
Activate a fault (remove battery fuse) and observe:
- the Fault indicator starts to blink
- a fault warning is displayed
- the internal buzzer is turned ON
- the Fault Warning Routing Equipment (FWRE) output is activated (if any)
11
Verify all conditions, i.e.:
- Fire Alarm condition
- Fire Warning condition
- Fault Warning condition
- Disablement condition
- Test condition
12
On completion of checks, ensure that only the green "Power" indicator is ON when the panel
is in its idle state (normal operation).
13
Enable alarm transference to the Fire Alarm Routing Equipment -FARE output.
The battery should be changed every 4 years. If a fault arises on the
panel that cannot be rectified, contact your nearest Autronica Fire and
Security office for qualified assistance.
13.1.3 SIL2 Approved Systems
For SIL2 approved systems, service and maintenance shall be carried
out according to the proof test intervals stated on the
AutroSafe 4 Oil&Gas SIL2 (G2) certificate with registration number
44 207 11 555929-001.

Table of Contents

Other manuals for Autronica Autro Safe

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autro Safe and is the answer not in the manual?

Autronica Autro Safe Specifications

General IconGeneral
BrandAutronica
ModelAutro Safe
CategorySmoke Alarm
LanguageEnglish