Appendix B - Power Supply
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. I, 2014-04-01,
Autronica Fire and Security AS
Page 86
15.13.2 Battery Input
The battery input is protected by an electronic short-circuit detector
and a regular fuse. If a short circuit is detected, the battery relay will
turn OFF within approx 50ms. The AutroSafe AutroFieldBus system
will then report “Battery not connected”.
15.14 Part of an AutroFieldBus Network
As a part of an AutroFieldBus network, the power module is
configured before start-up using dipswitches, some data, for example,
“Low voltage”-warning is given from an AutroSafe configuration via
AutroFieldBus.
Diagnostic outputs are given onboard with LEDs and alarm relay, and
on AutroSafe panels with audible alarms and display messages.
The LEDs and fault relay will not indicate any failure before the
AutroSafe has AutroFieldBus connection and the AutroSafe system
has been initialized.
15.15 Power Unit BPS-405 / BPS-410 as Standalone
In the standalone system, user input is given during installation only,
using dipswitches onboard. Set dipswitch S6.3 OFF to set the power
supply in standalone mode.
Diagnostic outputs are given onboard with LEDs and fault relay.

Table of Contents

Other manuals for Autronica Autro Safe

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autro Safe and is the answer not in the manual?

Autronica Autro Safe Specifications

General IconGeneral
BrandAutronica
ModelAutro Safe
CategorySmoke Alarm
LanguageEnglish