Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. I, 2014-04-01,
Autronica Fire and Security AS
Page 24
5.7 Mounting Power Supply Unit BPS-405 / BPS-410
The unit can be mounted inside a rack or consol. The hole and screw
dimensions are shown below.
Note that the BPS-410 Power Supply Unit 24VDC/10A is delivered as
two separate part numbers:
116-BPS-410 for 230VAC
116-BPS-410/115 for 115VAC
The dipswitch settings on the Power Board BSF-400 (dipswitch S6-6)
determines the type of power unit.
Dip-switch
Name
Description
S6-6
Power Unit Type
ON: BPS-405
OFF: BPS-410
For further information on dipswitch settings, refer to Appendix B –
Power Supply. Note that when using Power Unit BPS-410 (including a
24V/10A power supply), a calibration procedure must be performed.
Refer to the Commissioning Handbook, Calibration Procedure
Power Unit BPS-410.