Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. I, 2014-04-01,
Autronica Fire and Security AS
Page 23
Instructions
Remarks
Illustrations
Power must not be
applied before
commissioning.
At a later stage
(during
commissioning)
interconnect the other
plus pole and minus
pole on the batteries
with the cable.
Locate the wire (Part
No. 116-XL-069)
connected to the
Power Board (Therm
+ and Therm-), then
fasten the
temperature sensor
on the other end of
the cable to the
battery with a piece of
tape.
Make sure that the
sensor itself is
securely fastened
close to the battery.
The length of the
temperature sensor
wire must not exceed
3m. Make sure that
the wire is not placed
close to other wires
that conduct high
current, as for
example, wires for
sounder circuits,
230VAC or 24VDC.
-
+
!
POWER OFF!