Service and Maintenance
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. I, 2014-04-01,
Autronica Fire and Security AS
Page 59
13. Service and Maintenance
The AutroSafe Interactive Fire Alarm System provides a Log Menu,
which records all system events, i.e. fire alarms, prealarms, faults,
enablements/disablements, user operations and tests.
It is the system owner’s or authorized personnel’s duty to register all
events in a Control Journal.
13.1.1 Monthly Maintenance
Step
Description
1
Look through the log journal to find any possible irregularities.
2
Make sure that possible changes in the building structure or storage environment have not
affected the detectors’ capability to detect a potential fire.
3
Make sure that the detectors are not covered with paint or contaminated with dust or dirt.
Check the log for contaminated detectors (Service/Log menu).
4
Perform a visual inspection of the panels/cabinet.
5
Perform a simple test of display and panel functions
6
Test the sounders.

Table of Contents

Other manuals for Autronica Autro Safe

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica Autro Safe and is the answer not in the manual?

Autronica Autro Safe Specifications

General IconGeneral
BrandAutronica
ModelAutro Safe
CategorySmoke Alarm
LanguageEnglish