Appendix A - Controller Board BSA_400
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. I, 2014-04-01,
Autronica Fire and Security AS
Page 74
Fault category: Power
Fault message
Cause
Remedy
BSF-400 Output [A1/A2/B1/B2/C1/C2]
fuse blown
Fuse Fault LED blinking
General Fault LED blinking
The fuse is blown.
Replace with appropriate
fuse
BSF-400 Output [A1/A2/B1/B2/C1/C2]
voltage to low.
General Fault LED blinking
This may occur when
running on battery only
and battery voltage is
below 18V.
Insert mains to charge
batteries.
This warning may occur
when a fuse is removed
from an output with no
load.
Accept fault in AutroSafe.
BSF-400 Battery Relay Fault
This warning may occur
during start-up if a
battery is not connected
Connect battery, or put
dip switch 5 to OFF
position if no battery is to
be used
The relay fault warning
may occure if there is a
hardware fault.
Replace BSF-400 board.
BSF-400 Battery voltage to low
This message may occur
under start-up when
battery voltage is to low,
i.e. charging current is
>1100mA.
Message will clear when
charge current drops
below 400mA.