EasyManuals Logo

Autronica AutroGuard Multicriteria Protector V-430 Series User Manual

Autronica AutroGuard Multicriteria Protector V-430 Series
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #115 background imageLoading...
Page #115 background image
Testing and Maintenance
AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339-4, 2022-12-09,
Autronica Fire and Security AS
Page 109
The below pop-up window will appear
Confirm by clicking ‘OK’:
4. Wait about 90 seconds until the ‘finished’ message appears
in the notification window:
If the base has higher FW than 1.9.4 you will also see 2 restarts:
5. Confirm that the fault is gone by clicking ‘Reset’. If possible
do an Power OFF and then a new loop scan with AS2000.
Wait for about 10 minutes to see if there are any covered
faults.
If the fault still appear after trying any of these methods several
times, the AutroGuard Protector must be replaced. Register the serial
number(s) of the protector(s) and copy the AS2000 logs.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroGuard Multicriteria Protector V-430 Series and is the answer not in the manual?

Autronica AutroGuard Multicriteria Protector V-430 Series Specifications

General IconGeneral
BrandAutronica
ModelAutroGuard Multicriteria Protector V-430 Series
CategoryFire Alarms
LanguageEnglish

Related product manuals