40 Cyclades ACS 5000 Installation/Administration/User Guide
To view and reset IPDU information [Expert]:
1. Select Expert - Applications - IPDU Power Power Mgmt. - View IPDUs Info. The View IPDUs
Info screen appears.
2. To clear the stored values, click the Clear Max Detected Current button or the Clear Max
Detected Temperature button.
Applications - IPDU Power Mgmt. - Configuration
An administrator can select Expert - Applications - IPDU Power Mgmt. - Configuration to
configure each configured IPDU.
NOTE: The operating parameters may differ depending on the make and model of IPDU.
Table 6.3: Expert - Applications - IPDU Power Mgmt. - View IPDUs Info Description
Screen Heading Description Example
ID Either a default name or administrator-configured IPDU ID
appears followed by the serial port number to which the
IPDU is connected in parentheses.
i1A (serial port 1)
Model The model of supported IPDU connected to the console
server at the designated port.
Cyclades PM8
Number of Outlets The number of outlets on the IPDU. 8
Number of Inlets Total number of inlets available on the target IPDU. 1
Syslog Whether syslogging has been configured for messages
from this IPDU.
ON when syslogging is
configured
Buzzer Whether a buzzer has been configured to sound when a
specified alarm threshold has reached.
ON when the buzzer is
configured
Software Version IPDU firmware version installed on the IPDU. 1.7.0
Polling Rate The time interval at which the IPDU is polled by the PMD. 10000 ms
Current [value] The instantaneous current measured from the IPDU at
this time.
1.3 A
Threshold Max. The maximum current that can be reached before an
alarm is initiated or the buzzer sounds, or both.
20.0 A
Max Detected The recorded maximum current reported by this IPDU
(which may include transients).
1.3 A