A 20
5rt -xx
Reset: current register values (increment)
t:=5
to
t:=9
r: desired reset index (r:=0 or r:=1 to 9):
0 actual current register value
1 at last reset
2 at second last reset
... etc.
t: Demand rate (t:=5 to t:=9)
5 Total
6 Demand rate 1
7 Demand rate 2
... etc.
xx: desired value (Counter/Total)
00 Counter 1
01 Counter 2
... etc.
15 Counter 16
64 positive Total 1
65 positive Total 2
66 positive Total 3
67 positive Total 4
80 negative Total 1
81 negative Total 2
82 negative Total 3
83 negative Total 4
Table value:
d d d d d d d d
dddddddd: current register value
Example:
0 0 0 1 2 3 4 5
Expl.: The current register value is (was) 12345
600 -00
Number of counters (number of pulse inputs defined in the DLX)
Table value: n n
nn: Number of counters
Example: 1 6
Expl.: The DLX is currently programmed to use 16 pulse inputs.
600 -01
Number of totals (number of totaling units defined in the DLX)
Table value: s
s: Number of totals
Example: 4
Expl.: The DLX is currently programmed to use 4 totaling units.
600 -02
Number of rates (energy and demand)
Table value: e d
e: Number of energy rates
d: Number of demand rates
Example: 2 2
Expl.: The DLX is currently programmed to use 2 energy rates and 2 demand
rates.
600 -03
Number of apparent demand calculations
Table value: s
s: Number of apparent demand calculations
Example: 2
Expl.: The DLX is currently programmed to calculate 2 apparent demand values.