A 28
82x -yy Assignment of load profile storage areas
x: 1 Load profile MP1
2 Load profile MP2
3 Load profile MP3: not implemented in DLX
yy: 00 for the first three codes (0, 1, 2)
01 for the next three codes (3, 4, 5)
:
K/3 for codes K, K+1, K+2
Code 0 stands for Counter 1 (yy=00 1--)
1 Counter 2 (yy=00 -2-)
2 Counter 3 (yy=00 --3)
3 Counter 4 (yy=01 1--)
: :
15 Counter 16 (yy=05 1--)
64 positive total 1 (yy=21 -2-)
65 positive total 2 (yy=21 --3)
66 positive total 3 (yy=22 1--)
67 positive total 4 (yy=22 -2-)
80 negative total 1 (yy=26 --3)
81 negative total 2 (yy=27 1--)
82 negative total 3 (yy=27 -2-)
83 negative total 4 (yy=27 --3)
96 apparent demand 1 (yy=32 1--)
97 apparent demand 2 (yy=32 -2-)
104 Cos ϕ 1+ (yy=34 --3)
105 Cos ϕ 2+ (yy=35 1--)
112 Cos ϕ 1- (yy=37 -2-)
113 Cos ϕ 2- (yy=37 --3)
Table value: t t d t t d t t d
tt: 00 if no value is stored
10 for storage of the demand value
20 for storage of the total energy value
21 for storage of the energy value for rate 1
22 for storage of the energy value for rate 2
23 for storage of the energy value for rate 3
24 for storage of the energy value for rate 4
d: number of digits for storage and transmission for this value. If tt =
00 this position contains a blank (“ “).
Example: Query to table address 821-00 (the first three codes for load profile MP1):
0 0 2 0 8 1 0 4
Expl.: 00: The value of code 0 will not be stored in load profile MP1,
208: The value of code 1 will be stored as a total energy value with 8 digits in
load profile MP1
104: The value of code 2 will be stored as a demand value with 4 digits in
load profile MP1