OPERATING PROCEDURES
RECOMMENDED START-UP PROCEDURES
4 - 4 I-E96-506B1
®
Table 4-3. Unloaded DC Bus Output Voltage Requirements
5 VDC 24 VDC +15 VDC -15 VDC
Min Max Min Max Min Max Min Max
5.1 5.3 25.7 26.0 15 15.75 -15 -15.75
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com