EasyManua.ls Logo

Bailey Infi 90 - Calculating Current Requirements; B-1. DC Current Consumption for INFI 90 Modules

Bailey Infi 90
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODULE POWER REQUIREMENTS
CALCULATING CURRENT REQUIREMENTS
B - 2 I-E96-506B1
®
4. Calculate the -15 VDC current requirement for each
cabinet.
a. Refer to Table B-1 for the -15 VDC current requirement
of each module.
b. Total the -15 VDC current requirement per cabinet.
5. Calculate the +24 VDC current requirement.
a. Refer to Table B-1 for the +24 VDC current requirement
for each module.
b. Table B-2 lists +24 VDC current requirements of termi-
nation units and termination modules.
c. Total the +24 VDC current requirement per cabinet.
6. Add the current requirement of any system powered I/O
using +24 VDC to the total from Step 5c. Table B-3 gives an
overview of how to calculate the system powered I/O current
requirement.
Table B-1. DC Current Consumption for INFI 90 Modules
INFI 90
Modules
No. of
Modules/
Cabinet
Current Consumption Per Module (mA)
5 V
Total
5 V
+15 V
Total
+15 V
-15 V
Total
-15 V
24 V
Total
24 V
IISAC01 0 0 0 530
IMAMM03 725 125 30 0
IMAOM01 1045000
IMASI02 95 30 25 0
IMASI03 330 140 40 0
IMASM01 1208545 0
IMASM02
IMASM03
4008040 6
IMASM04 5504530 0
IMASO01 530 220 225 50
IMCIS02 300 30 25 7
IMCOM03
IMCOM04
6605550 7
IMCPM01 0000
IMCPM02 825000
IMDSI02 60000
IMDSM04 1500 0 0 65
IMDSM05 600000
Total for page
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com