MAINTENANCE
EQUIPMENT REQUIRED
I-E96-506B1 6 - 3
EQUIPMENT REQUIRED
Following is a list of tools and equipment required for the
maintenance procedures.
•
Antistatic vacuum.
•
Digital multimeter.
•
Flathead torque screwdriver (Newton meters/inch-pounds).
•
Four-inch flathead screwdriver.
•
16-inch flathead screwdriver.
•
Isopropyl alcohol (99.5% electronic grade).
•
Foam-tipped swab.
•
Eberhard Faber (400A) pink pearl eraser or equivalent.
•
Fiberglass burnishing brush.
•
Lint-free cloths.
•
Small needle nose pliers.
PREVENTIVE MAINTENANCE PROCEDURES
This section covers tasks from Table 6-1 that require specific
instructions or further explanation. The tasks and instructions
covered are:
•
Cabinet air filter cleaning or replacement.
•
How to check signal, power and ground connections.
•
Checking modular power supply outputs.
•
The power entry panel preventive maintenance procedure.
•
Specific instructions on cleaning printed circuit boards and
edge connectors.
Refer to Section 7 for instructions on how to replace the fan
assembly.
Cabinet Filter Cleaning/Replacement
The cabinet air filter mounts over the lower air vent, inside the
cabinet front door. To replace the air filter:
1. Use a flathead screwdriver to remove one screw securing
the mounting plate at the top of the air filter mounting bracket.
Replace power modules. Call Bailey sales and service for information. 5 years
Complete all checks and inspections in this table. Replacement tasks should be done
at the scheduled frequency.