102 9424200994 Rev N
Setting Range Increment
Unit of
Measure
Default
C Coefficient
0 to 1
0.00001
C Coefficient
1.00000
N Coefficient
0.5 to 2.5
0.00001
N Coefficient
1.29690
K Coefficient
n/a
n/a
K Coefficient
0.02800
R Coefficient
0 to 30
0.00001
R Coefficient
0.50000
Voltage Restraint
Mode
Disabled, Control, or Restraint n/a n/a Disabled
Voltage Restraint
Setpoint
0 or 30 to 250 varies volts 0
* For protection systems equipped with two sets of CTs.