EasyManua.ls Logo

Basler BE1-11g - Page 410

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
398 9424200994 Rev N
Figure 281. BESTlogicPlus Settings (V1 Mode)
Table 143. Pickup Test Settings (V1 Mode)
Pickup Setting
Time Delay
78 V
50 ms
38 V
50 ms
22 V
50 ms
Step 4: Prepare to monitor the 27X-1 function operation. Operation can be verified by monitoring OUT2
(see Figure 281).
Step 5: Connect and apply a 240 Vac, single-phase voltage source to terminals C13 (A-phase) and C16
(neutral). For a single-phase input test, V1 = A-phase voltage / 3. Therefore, the BE1-11g
should pick up at a value of three times the setting value when applying only a single-phase
input. For example, to determine the pickup voltage value required for a BE1-11g with a pickup
setting of 78, it would require 78 times 3 or 234 volts of input voltage.
Step 6: Slowly decrease the A-phase voltage until OUT2 closes and record the pickup. Verify that there
is a 27X-1-V1 target on the front-panel display. Slowly increase the voltage until OUT2 opens
and record the reset. Reset the target.
Step 7: Verify the pickup and reset accuracy at 120 Vac for a pickup setting of 38 V (114 Vac on test
set) and 70 Vac for a pickup setting of 22 V (66 Vac on test set) as listed in Table 143. Record
the results.
Step 8: (Optional.) Repeat steps 1 through 7 for the B-phase and C-phase voltage inputs.
Step 9: (Optional.) Repeat steps 1 through 8 for settings group 1, 2, and 3.
Step 10: (Optional.) Repeat steps 1 through 9 for 27X-2, 27X-3, and 27X-4.
Timing Verification (V1 Mode)
Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Undervoltage (27X-1) screen and send
the first row of test settings in Table 144 to the BE1-11g for settings group 0.
Table 144. Timing Test Settings (V1 Mode)
Pickup Setting
Time Delay
38 V
2,000 ms
38 V
5,000 ms
38 V
10,000 ms
Step 2: Prepare to monitor the 27X-1 timings. Timing accuracy is verified by measuring the elapsed
time between a sensing voltage change and OUT1 closing.
Step 3: Connect and apply a 120 Vac, single-phase voltage source to terminals C13 (A-phase) and C16
(neutral).
Step 4: Step the voltage down to 110 volts. Measure the time delay and record the result.
Auxiliary Undervoltage (27X) Test BE1-11g

Table of Contents

Related product manuals