EasyManua.ls Logo

Basler BE1-11g - Page 490

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
478 9424200994 Rev N
Figure 307. BESTlogicPlus Settings (87R)
Step 8: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the
pickup. This should occur at 0.30 A ±0.05 A. Verify that there is an 87A target on the front-panel
display.
Step 9: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 reopens and record the
dropout. See the functional test report for acceptable ranges.
Step 10: To test the Restraint Slope 1 setting, connect two balanced three-phase current sources to the
BE1-11g in ABC rotation: 3.00°, 3.0120°, 3.0120° amps to terminals D1 through D6 and
3.0180°, 3.060°, 3.060° amps to terminals F1 through F6 (1.5x tap).
Step 11: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the
pickup. This should occur at 3.75 A ±0.08 A. Verify that there is an 87A target on the front-panel
display.
Step 12: Reset to the current levels in Step 9 and reset all targets.
Step 13: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the
pickup. This should occur at 2.40 A ±0.05 A. Verify that there is an 87A target on the front-panel
display.
Step 14: To test the Restraint Slope 2 setting, connect two balanced three-phase current sources to the
BE1-11g in ABC rotation: 6.50°, 6.5120°, 6.5120° amps to terminals D1 through D6 and
6.5180°, 6.560°, 6.560° amps to terminals F1 through F6 (3.25x tap).
Step 15: Slowly increase the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the
pickup. This should occur at 8.83 A ±0.18 A. Verify that there is an 87A target on the front-panel
display.
Step 16: Reset to the current levels in Step 12 and reset all targets.
Step 17: Slowly decrease the A-phase current in CT circuit 1 or 2 until OUT2 closes and record the
pickup. This should occur at 5.10 A ±0.10 A. Verify that there is an 87A target on the front-panel
display.
Step 18: (Optional.) Repeat Steps 1 through 17 for the B-phase and C-phase current inputs.
Step 19: (Optional.) Repeat Steps 1 through 18 for settings group 1, 2, and 3.
Pickup Verification (Average Restraint)
Step 1: Use BESTCOMSPlus to send the operational settings in Table 220. Reset all targets.
Table 220. Operational Settings (87R - Average)
Setting
Value
BESTCOMSPlus Screen
Description
Nominal Phase
Voltage
69.3 V
System Parameters, Power System
Sets the nominal secondary
sensing voltage to 69.3 V
Phase Current Differential (87) Test BE1-11g

Table of Contents

Related product manuals