EasyManua.ls Logo

Basler BE1-11g - Page 500

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
488 9424200994 Rev N
Setting
Value
BESTCOMSPlus Screen
Description
Circuit 1 Ground
Compensation
No
System Parameters, Transformer
Setup
Disables the primary
winding zero sequence
trap
(Optional) Circuit
1 Diff. Circuit
Primary
System Parameters, Transformer
Setup
Establishes circuit 1 on the
primary side of the
transformer. For report
labeling purposes only.
Circuit 1 Polarity
Normal
System Parameters, Transformer
Setup
Sets the phase rotation of
circuit 1 for ABC
Circuit 1 Phase
Relationship
A
System Parameters, Transformer
Setup
Sets A-phase in circuit 1
equal to the phase
relationship setting for
circuit 2
Mode
Enabled
Protection, Current, Neutral
Differential (87N-1)
Enables the neutral
differential element
Iop Minimum (A)
2.00
Protection, Current, Neutral
Differential (87N-1)
Sets the minimum operate
current required for pickup
to 2 A
Time Delay (ms)
100
Protection, Current, Neutral
Differential (87N-1)
Sets the time to trip after a
pickup to 100 ms
Overcorrection
Coefficient
1.30
Protection, Current, Neutral
Differential (87N-1)
Sets the sensitivity of the
directional sensing by
using a factor of 1.30
CT Flip
No
Protection, Current, Neutral
Differential (87N-1)
Stipulates that IG is in
phase with 3I0 for internal
faults
CT Source
CT1, IG1
Protection, Current, Neutral
Differential (87N-1)
Sets the differential zone
with CT1 and IG1
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 309.
Blocking is disabled.
OUT1 closes for 87N-1 Trip.
OUT2 closes for 87N-1 Pickup.
Fault recording is enabled.
Figure 309. BESTlogicPlus Settings
Step 3: Prepare to monitor the 87N-1 function operation. Operation can be verified by monitoring OUT2
(see Figure 309).
Step 4: Connect a single-phase 60-Hz current source to terminals D1 and D2 (CT1 A-phase): 3.0 A
0°. Connect a single-phase current source to terminals D7 and D8 (IG input): 3.0 A 180°.
Verify that Iop is around zero amps.
Neutral Current Differential (87N) Test BE1-11g

Table of Contents

Related product manuals