EasyManua.ls Logo

Basler BE1-11g - Page 544

Basler BE1-11g
672 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
532 9424200994 Rev N
Figure 321. BESTlogicPlus Settings
Step 3: Steps 4 through 6 will initiate the 62-1 timer by changing the 43-1 switch state to ON (logic 1).
Once initiated, the 62-1 timer will force an output based on the 400 ms pickup time setting.
Step 4: Use the Metering Explorer of BESTCOMSPlus to open the Control, Virtual Switches tree branch
(Figure 322). Using select-before-operate, perform the following steps to control a virtual switch.
Figure 322. BESTCOMSPlus Virtual Switches Control Screen
Step 5: Click the 43-1 button to select it. Login may be required. The On or Off indicator (current state)
will begin to flash.
Note
If step 6 is not performed within 25 seconds of step 5, the indicator will
stop flashing and the 43-1 button will have to be selected again.
Step 6: Click on the 43-1 button a second time to operate it. After clicking Yes, the On or Off indicator
(previous state) will stop flashing and the On or Off indicator (current/new state) will light.
Step 7: Repeat steps 5 and 6 to change the state of the 43-1 switch to open and remove the initiate
input from the 62-1 timer.
Step 8: Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events
screen.
Step 9: Verify that the 43-1 switch change to an ON state was logged and approximately 400 ms later,
the 62-1 timer picked up. Then, sometime later, the 43-1 switch change to an OFF state was
logged and the 62-1 timer dropped out approximately 2,000 ms later. The state of the 43-1
switch in the SER report uses the programmable name parameters applied to the switch. Figure
323 illustrates the timing relationship of the 43-1 switch and 62-1 timer.
Logic Timers (62) Test BE1-11g

Table of Contents

Related product manuals