Controller terminals
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
198
of 314
7.12
CANopen
®
Type code BM5500, BM5600, BM5700 with CANopen
®
:
BM5XXX-XXXX-XXXX-03XX
X3
X4
CANopen
®
IN
CANopen
®
OUT
Memory 4 kByte DP-RAM, 256 kByte RAM,
1 MByte Flash-Eprom
Number of bus connections 2, no slot rules
Bus connection 2 connectors RJ45, 8-pole
Baud rates 20/125/250/500/1000 kBit/s
Address range 7 Bit; address 1 to address 127
Address setting DIP-switch
Short-circuit proof RJ45-connection Yes
Isolation Optocoupler, DC/DC-converter
1: CAN_H
2: CAN_L
3: GND
4: Reserved
5: Reserved
6: Reserved
7: GND
8: Reserved
X3
X4