7.10 Installation procedure
h Lay all cables EMC-compatible.
h Co
nnect cables (refer to ZWiring diagrams– from page 170).
(Observe the torques!)
h F
or all connections, attentions is to be paid to strain relief
The following steps must be carried out at installation:
1 Co
nnect the motor through terminals 1U2, 1V2, 1W2 and PE.
Ensure the proper phases when connecting (rotational direction).
Use toroidal cores if necessary, refer to ZAvoid b
earing currents– from page 165.
Observe the permitted torques!
2 Conn
ect fuses (S1) - not necessary for power modules
(in case you consider UL 508 C: use the UL-
listed semiconductor- or total-range-
fuses in chapter ZFuses– from
page 266).
3 Conn
ect mains filter (L2) - not necessary for power modules.
4 Conn
ect the power choke (L1) at the mains filter output
- no
t necessary for BM551X, BM5523, BM5524, BM5525
- no
t necessary for BM5XXX-XR/BM5XXX-XS/BM5XXX-XW
- no
t necessary for power modules
Connect the power modules with the DC link.
Connect devices BM5
51X, BM5523, BM5524, BM5525 and
BM5XXX-XR/BM5XXX-XS/BM5X
XX-XW with the mains filter.
DANGER!
Risk of
fatal injury from electrical current!
Electrically live parts are life-threatening.
Therefore:
m Make certain that the parts to be mounted (e.g. power supply cables) and the
mounting areas are de-energized for the entire duration of mounting the device.
NOTE!
Steps which are not necessary for the installation of b maXX power modules are
marked.
NOTE!
Pay attention to connect the power supply with clockwise rotating field.
Connection to a power supply with clockwise rotating field is not required for