EasyManua.ls Logo

Baumuller b maXX 5500 - Electrical Data BM557 X Universal Units

Baumuller b maXX 5500
316 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical data basic units
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
84
of 314
3.4
3.4.1.7 Electrical data BM557X universal units
BM5572 - A/F BM5573 - A/F
Rated input power
1)2)
328 kVA 412 kVA
Rated input current
1)2)
(I
eff
) 474 A 594 A
Total harmonic distortion input current
1)2)
(THD
I
) 54 %
Max. input current
2)
(I
eff
) 602 A 760 A
DC link rated voltage
1)
540 V
DC
DC link capacitance (internal) 19.8 mF
DC link capacitance (external), permitted Refer to ZPage 220
DC link discharging time
(internal DC link capacitance)
100 s 120 s
Waiting time between two switching-on operations None
Output voltage
1)3)
(U
AC
) 3 x 0 V bis 3 x 370 V
Output frequency at 4 kHz
14)
0 Hz bis 450 Hz
Rated output current
1)5)6)7)13)15)
(I
AC
) at 4 kHz
4)
450 A 615 A
Rated output current
1)5)6)7)13)15)
(I
AC
) at 8 kHz
4)
338 A 420 A
Output peak current
1)5)6)8)15)
(I
AC
) at 4 kHz
4)
585 A 800 A
Output peak current
1)5)6)8)15)
(I
AC
) at 8 kHz
4)
439 A 545 A
Max. peak current period
9)
60 s
Connected load DC link terminals Max. 250 kW Max. 315 kW
Brake resistor current, permitted (Î) Max. 300 A
Brake resistor, external 2.6
Brake resistor threshold (Û)
12)
780 V
Brake resistor peak power 234 kW
Permitted continuous brake resistor power external 180 kW
Power loss referring to power input 4700 W 6450 W
Power loss referring to control voltage 116 W
Power loss of the device fan referring to 400 V
AC
Max. 540 W
Current of integrated brake control Max. 8.0 A
11)
Cooling air requirement power heatsink 1000 m
3
/h
Cooling air requirement device internal space 250 m
3
/h

Table of Contents