Installation
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10
189
of 314
7
7.11.3 Electrical connection power unit
Power system
1U1, 1V1, 1W1, PE
Max. cross-section
of connection
Connection
technology
Torque Load capacity
not valid for
power modules
BM551X 2.5 mm
2
Terminal block - Refer to
ZFu
ses from
page 266
BM552X 4.0 mm
2
Screw terminal Min. 0.5 Nm
Max. 0.6 Nm
BM553X
BM56
3X
25 mm
2
Screw terminal Min. 2 Nm
Max. 2.3 Nm
BM554X
BM564X
50 mm
2
Screw terminal Min. 6 Nm
Max. 8 Nm
BM555X
BM565X
BM575X
2 x 95 mm
2 1)3)
Cable lug
for M8
Min. 10 Nm
Max. 13 Nm
BM556X
BM566X
BM576X
2 x 185 mm
2 2)3)
Cable lug
for M10
Min. 12 Nm
Max. 25 Nm
BM557X
BM577X
2 x 185 mm
2 2)
4 x 95 mm
2 1)
Cable lug
for M10
Min. 12 Nm
Max. 25 Nm
1)
The cable lug may be 25 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 95 mm
2
, you may also use stronger
cables than 95 mm
2
. Also refer to ZCables power supply-device from page 246.
2)
The cable lug may be 35 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 185 mm
2
, you may also use stron-
ger cables than 185 mm
2
. Also refer to ZCables power supply-device from page 246.
3)
One cable of the mentioned cross section is sufficient for the operation.