EasyManua.ls Logo

Baumuller b maXX 5500 - Environmental Temperature; Supply Voltage

Baumuller b maXX 5500
316 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10
55
of 314
3
3.3.5.2 Environmental temperature
The BM5500, BM5600, BM5700 were designed to be operated at an environmental tem-
perature of T
Rated
= 40 °C. If the devices are operated at temperatures between 40 °C
and 55 °C the permitted output current (I
O
) must be reduced according to the following
formula:
The coolant temperature complies with the environmental temperature of air-cooled de-
vices and with the water temperature of water-cooled devices.
3.3.5.3 Supply voltage
Above
rated supply
voltage
The rated voltage is 3 x 400 V
When having input voltages above the rated supply voltage the output currents must ac-
cordingly be reduced at a constant output power.
Figure 27: Output current in dependence of the power supply voltage
Below
rated supply
voltage
The rated voltage is 3 x 400 V
The output power of the device reduces with lower power supply voltages.
Figure 28: Reducing the output voltage in dependence of the power supply voltage
I
O
I
O40°C
1
Coolant temperature- 40°C
°C
--------------------------------------------------------------------
003




=
Output current device
Power supply voltage
180 V 400 V 528 V
100 %
50 %
Output voltage device
Power supply voltage
207 V
400 V
528 V
177 V
370 V
498 V

Table of Contents