Cabling
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
246
of 314
11.1
11.1 Cabling
11.1.1 Cables power supply-device
Device Number of wires x
cross section
1)
Connection to device
3)
Maximum length
2)
BM551X 4 x 0.5 bis 2.5 mm
2
(AWG 16 - 12)
Flexible cable
with
/without wire end ferrule
(terminal block)
Power supply to mains filter:
user-defined
mains filter to power choke/
device:
max. 30 cm
BM552X 4 x 0.5 to 4 mm
2
(AWG 24 - 10)
Flexible cable with wire end ferrule
(s
crew terminal)
BM5532
BM5533
BM5534
4 x 0.5 to 10 mm
2
(AWG 20 - 6)
Flexible cable with wire end ferrule
(s
crew terminal)
BM5535
4)
4 x 16 mm
2
63 A-fuses must be provided
for
the cable protection and a
cable with 16 mm
2
cross sec-
tion must be used.
Pin-cable-lugs according to DIN
46230
The terminals at the BM5535 are provided for
cross sections up to 10 mm
2
, therefore at the
BM5535 pin-cable-lugs according to DIN 46230
must be used.
BM5632 4 x 25 mm
2
63 A-fuses must be provided
for
the cable protection and a
cable with 25 mm
2
cross sec-
tion must be used.
Flexible cable with wire end ferrule
(screw terminal)
BM554X
BM564X
4 x 16 to 50 mm
2
(AWG 6 -0)
Flexible cable with wire end ferrule
(s
crew terminal)
BM555X
BM565X
BM575X
4 x 25 to ca. 185 mm
2
Cable lug max. width: 25 mm
(current bar)
4)
BM556X
BM566X
BM576X
Cable lug max. width: 35 mm
(current bar)
5)
BM557X
BM577X
Max. 4 cables with
(4 x 95 mm
2
)
Max. 2 cables with
(4 x 185 mm
2
)
Cable lug max. width: 25 mm or
35 mm (current bar)
6)
1)
Possible cross section
For UL conform machines/installations you must use
UL certified circuit cables.
2)
The length of the cable between mains filter and power supply is not of importance for the compliance to the EMC regulation.
3)
The installing of the cables is user-defined.