EasyManua.ls Logo

Baumuller b maXX 5500 - Electrical Data BM57 XX Continuous Current Unit

Baumuller b maXX 5500
316 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10
97
of 314
3
3.4.3 Electrical data BM57XX continuous current unit
m Without charging resistor BM57XX-XT/BM57XX-XG/BM57XX-XI
BM5755
15)
BM5766
14)
BM5773
Rated input power
1)2)
139 kVA 306 kVA 475 kVA
Rated input current
1)2)
(I
eff
) 190 A 442 A 685 A
Total harmonic distortion input current
1)2)
(THD
I
) 40 % 50% 54 %
Max. input current
2)
(I
eff
) 380 A 455 A 772 A
Rated DC link voltage
1)
540 V
DC
DC link capacitance (internal) 7140 F 13.2 mF 19.8 mF
DC link capacitance (external), permitted Refer to ZPa
ge 220
DC link discharging time
(internal DC link capacitance)
140 s 230 s 150 s
Waiting time between two switching-on operations no
Output voltage
1)3)
(U
AC
) 3 x 0 V to 3 x 370 V
Output frequency at 4 kHz
13)
0 Hz to 450 Hz
Rated output current
1)5)6)7)14)
(I
AC
) at 4 kHz
4)
260 A 450 A 720 A
Rated output current
1)5)6)7)14)
(I
AC
) at 8 kHz
4)
185 A 305 A 495 A
Output peak current
1)5)6)8)14)
(I
AC
) at 4 kHz
4)
260 A 450 A 800 A
Output peak current
1)5)6)8)14)
(I
AC
) at 8 kHz
4)
185 A 305 A 545 A
Max. peak current period
8)
no limit
60 s
Connected load DC link terminals - Max. 160 kW Max. 360 kW
Brake resistor current, permitted (Î) - Max. 236 A Max. 300 A
Brake resistor, external 5
3,33 2,6
Brake resistor threshold (Û)
11)
780 V
Brake resistor peak power 120 kW 183 kW 234 kW
Permitted continuous brake r
esistor power external 80 kW 130 kW 180 kW
Power loss referring to
power input 3000 W 4800 W 7800 W
Power loss referring t
o control voltage 75 W 93 W 116 W
Power loss of device fan
referring to 230 V
AC
9)
190 W 174 W -
Current of integrated brake control Max. 8.0 A
10)
Cooling air requirement device internal space 135 m
3
/h 200 m
3
/h -
Requirement to the water c
ooling Refer to ZPage 59

Table of Contents