3.3.4 Required environmental conditions
Transport temperature range - 25 °C to + 70 °C
Transport climatic category
EN 60721-3-2
2 K 3
Storage temperature range - 25 °C to + 55 °C
Storage climatic class
EN 60721-3-1
1 K 4
Operation environment Industrial system
1)
Category C2 according EN61800-3
for operation in Second Environment
Operation temperature range Min. 5 °C to max. 55 °C
(with de
rating above 40 °C)
3)
Operation climatic class
EN 60721-3-3
3 K 3
Operating altitude Up to 4000 m above MSL,
exce
pt BM551X, BM5526, BM5527 up to 2000 m
(with derating above 1000 m)
2)
Humidity (operation)
EN 60721-3-3
Relative humidity: 5 % to 85 % no condensation
and
absolute humidity: 1 g/m
3
to 25 g/m
3
Ionizing and non-ionizing radiation < measurable range
Vibration, shock and repetitive shock
EN 61800-5-1, section 5.2.6.4 Vibration test
Max. 0.5 g during operation
Degree of pollution
EN 61800-5-1, table 6, Tab. 2
2
1)
For the operation in an environment of category C2 according to IEC 61800-3:2012, additional measures may be required.The manu-
facturer of the installation / user must provide the following evidence in this case:
The additional measures are effective. The specified
limit values of category C2, which are described in IEC 61800-3, are complied with.
2)
Refer to correction factors at environmental conditions, ZOperating altitude– on page 54.
3)
Refer to correction factors at environmental conditions, ZEnvironmental temperature– on page 55
NOTICE!
Normally, non-conductive pollution occurs. Conductive pollution is unacceptable.
Conductive pollution can lead to the destruction of the device. The customer is re-
sponsible for destructions, which were caused by pollution due to conductive materi-