Monitoring functions
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
238
of 314
10.2
10.2 Monitoring functions
Monitoring function Warning/error
Warning
Error
Adjustable
threshold
Adjustable
reaction
Reaction
pulse inhibit
Mains voltage Mains undervoltage X X - - X
Mains overvoltage X X - - X
Phase monitoring Phase failure X X - - X
Mains failure X X X - X
1)
Ground fault Fault current to ground - X - - X
Overcurrent Motor overcurrent - X - - X
DC link DC link overvoltage - X - - X
DC link relative undervoltage X X - - X
Overload monitoring Peak current not possible at this
time
X - - - -
Heat sink temperature Temperature > threshold 1 X - X - -
Temperature > switch-off threshold - X - - X
Temperature of
device interior
Temperature > threshold 1 X - X - -
Temperature > switch-off threshold - X - - X
Motor temperature I
2
t threshold exceeded - X X - X
Threshold 1 exceeded
2)
X - X - -
Threshold 2 exceeded
2)
X - X - -
Sensor short-circuit and/or
temperature < -30 °C
2)
- X - - -
Sensor not connected and/or
temperature > 250 °C
2)
- X - - -
Maximum temperature exceeded
2)
- X X - X
Position controller Dynamic position deviation - X X X -
Static position deviation - X X X -
Encoder 1 Cable break - X X X -
Cable break (SIN
2
+ COS
2
) - X X X -
Excessive rotational speed - X X X
3)
1)
Pulse inhibit carried out after a set time interval
2)
Only if KTY/PT1000 sensor used
3)
Adjustable
X: Implemented
-: Not possible