Cabling
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
248
of 314
11.1
11.1.2 Cables device-motor
Device Number of wires x
cross section
1)
Maximum length
2)3)
Connection to device
BM551X 4 x 1 bis 2.5 mm
2
(AWG 16 - 12)
100 m Flexible cable with/without wire
e
nd ferrule (terminal block)
BM552X 4 x 2 bis 4 mm
2
(AWG 24 -10)
1.5 bis 2.5 mm
2
: 100 m
From 4 mm
2
: 60 m
Flexible cable with wire end fer-
rule (screw terminal)
BM553X 4 x 4 bis 16 mm
2
(AWG 20 - 4)
60 m
BM554X 4 x (16 to 50 mm
2
)
(AWG 6 - 0)
Up to 25 mm
2
: 60 m
From 35 mm
2
: 50 m
BM555X
BM575X
4 x (20 to ca. 185 mm
2
) Up to 50 mm
2
: 50 m
> 50 mm
2
: 15 m
Cable lug max. width5
25 mm (current bar)
4)
BM556X
BM576X
Cable lug max. width:
35 mm (current bar)
6)
BM557X
7)
BM577X
7)
Max. 4 cables each with
(4 x 95 mm
2
)
Max. 4 cables each with
(2 x 185 mm
2
)
At 95 mm
2
: 15 m
At 185 mm
2
: 30 m
Cable lug max. width: 25 mm or
35
mm (current bar)
7)
1)
Possible cross section
Use a screened circuit Baumüller-line, optical shield cove
rage > 85%. Do not use single conductors.
For UL conform machines/installations you must use
UL certified circuit cables.
2)
Only for Baumüller cables with this maximum length and by usage of a Baumüller mains filter you can assume, that the limit values of
the EMC product standard EN 61800-3 are complied with.
3)
In case you use parallel-installed motor cables, the maximum length is to be reduced by the factor 1/n.
4)
After January 2018 delivery date: The devices provide connection terminals for larger cable cross-section.
5)
Connection lugs (current bars). Position refer to ZFigure 93– on page 184 .
Screw maximum two cable lugs to the current bar - one on the front side, one on the reverse
side of the bar.