11.3.4 Electrical data mains filter
TN/TT systems
BFN 3-1-... -001 0007 0016 0030 0042 0056 0075 0100 0130 0180
Max. input supply voltage 3 x 480 V
AC
+10 %,
50/60 Hz
Rated current
(at T
B
= 50 °C)
7 A 16 A 30 A 42 A 56 A 75 A 100 A 130 A 180 A
Peak current
(at T
B
= 50 °C)
1.5 x I
N
for < 1 min per hour
Current derating
Test voltage Line - line: 2125 V
DC
/ 2 s
Line - housing: 2125 V
DC
/ 2 s
Connection L1/L2/L3: safe-to-touch screw terminals
PE
connection: bolt M5 / M6 / M10
Maximum connection
cross-section
4
mm
2
4
mm
2
10
mm
2
10
mm
2
16
mm
2
25
mm
2
50
mm
2
50
mm
2
50
mm
2
Power loss (typical) 4 W 8 W 12 W 15 W 18 W 24 W 24 W 30 W 35 W
Protection class IP 20
EPCOS B84143A0150R410
Max. input supply voltage 3 x 480 V
AC
+10 %,
50/60 Hz
Rated current
(at T
B
= 50 °C)
150 A
Peak current
(at T
B
= 50 °C)
1.5 x I
N
for < 1 min per hour
2.5 x I
N
for < 1 min per hour
Test voltage Line - line: 2240 V
DC
/ 2 s
Line - housing: 2720 V
DC
/ 2 s
Connection L1/L2/L3: safe-to-touch screw terminals
PE: bolt
M10
Maximum connection
cross-section
95 mm
2
Protection class IP 20
II
rated
85
ambient
35°C
--------------------=

Table of Contents