Wiring diagrams
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
192
of 314
7.11
7.11.4 Requirements for the screwing
X100 (SELV/PELV) Max. cross-section
of connection
Connection
technology
Load capacity
24 V power supply 1.5 mm
2
Terminal block X100-1, X100-2, X100-5 and X100-
6: max. 8.0 A,
if you consider UL508C: max. 4.0 A
NOTICE!
It is forbidden to connect both the signal bus X300 and the power supply bus/brake
resistor bus X100:3/X100:4. This leads to damage of the devices!
Refer to ZConnection of several devices to the DC link without using the signal bus–
on page 177.
X101 (SELV/PELV) Max. cross-section
of connection
Connection
technology
Load capacity
Brake BM551X
BM552X
1.5 mm
2
Terminal block X101-1 bis X101-4:
Min. 0.1 A, max. 0.5 A
BM5532
BM5533
1.5 mm
2
Terminal block X101-1 bis X101-4:
Min. 0.1 A, max. 1.0 A
BM5632
BM5534
BM5535
BM5X4X
BM5X5X
BM5X6X
BM5X7X
BM57XX
1.5 mm
2
Terminal block X101-1 bis X101-4:
Min. 0.1 A, max. 8.0 A
if you consider UL508C:
max. 4.0 A
NOTE!
A relay with varistor protection circuit is required in case the customer connects an
additional relay.
NOTE!
Follow the mentioned torques to ensure an adequate conductivity.