Motor
1U2, 1V2, 1W2, PE
Max. cross-section
of connection
Connection tech-
nology
Torque Load capacity
BM551X 2.5 mm
2
Terminal block - Is limited by
the device,
also refer to
ZT
echnical
Data from
page 29
BM552X 4.0 mm
2
Screw terminal Min. 0.5 Nm
Max. 0.6 Nm
BM553X
BM563X
16 mm
2
Screw terminal Min. 2 Nm
Max. 2.3 Nm
BM5543
BM5544
BM5641
BM5642
50 mm
2
Screw terminal Min. 6 Nm
Max. 8 Nm
BM5545
BM5546
BM5645
50 mm
2
Screw terminal Min. 6 Nm
Max. 8 Nm
95 mm
2 4)
Screw terminal Min. 15 Nm
4)
Max.20 Nm
4)
BM555X
BM575X
2 x 95 mm
2 1)
Cable lug
for M8
Min. 10 Nm
Max. 13 Nm
BM556X
BM576X
2 x 185 mm
2 2)3)
Cable lug
for M10
Min. 12 Nm
Max. 25 Nm
BM557X
BM577X
2 x 185 mm
2 2)
4 x 95 mm
2 1)
Cable lug
for M10
Min. 12 Nm
Max. 25 Nm
Installation
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10
191
of 314
7
1)
The cable lug may be 25 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 95 mm
2
, you may also use stronger
cables than 95 mm
2
. Also refer to ZCables power supply-device from page 246.
2)
The cable lug may be 35 mm wide at most. The maximum cable diameter is dependent on the cable lug. In
case the cable lug, which you use, can safely clamp a stronger cable than 185 mm
2
, you may also use stron-
ger cables than 185 mm
2
. Also refer to ZCables power supply-device from page 246.
3)
One cable of the mentioned cross section is sufficient for the operation.
4)
After January 2018 delivery date: The devices provide connection terminals for larger cable cross-section.
Fan
X36
Max. cross-section of
connection
Connection
technology
Load capacity
BM5X4X-S/-A
BM5X5X-S/-A
BM5X6X-S/-A
BM5X7X-A
4.0 mm
2
Spring-loaded
connector
Max. 1.0 A
1)
1)
For fuse protection a fuse with the tripping characteristic „delayed“ must be used.