Operation
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10
229
of 314
8
8.4.4 POWERLINK
®
.
Type code b maXX BM5500, BM5600, BM5700 with POWERLINK
®
:
BM5XXX-XXXX-XXXX-04XX-
b maXX BM5500, BM5600, BM5700 devices can communicate with a POWERLINK
®
Managing Node via the fieldbus connection POWERLINK
®
.
X3 and X4 on the front side of the device are the RJ45 connections for POWERLINK
®
(also refer to ZController terminalson page 193).
Mounting and
installation
The mounting/installation consists of the following steps:
1 De-energize the b maXX BM5500, BM5600, BM5700 device
2 Set the b maXX BM5500, BM5600, BM5700 IP-address,
refer to ZSetting the IP address with address switchesfrom page 133
3 Connect b maXX BM5500, BM5600, BM5700 with Ethernet-connection cables.
n Please, observe an EMC-compatible laying of the Ethernet connection cables!
n The following cables were released for use by Baumüller:
Ethernet-connection cable;
Further information refer to ZAccessories Ethernet/EtherCAT
®
/VARAN/
POWERLINK
®
.on page 292.
Commissioning. The following preconditions must be fulfilled before commissioning:
1b maXX BM5500, BM5600, BM5700 with POWERLINK
®
is installed correctly.
n Ethernet-connection cables are wired correctly.
2 The control cabinet is properly locked and all safety devices are operating.
3 The b maXX BM5500, BM5600, BM5700 device is ready-to-use.
Address switch By means of the address switches S3 and S4 the last byte of the IP-address is set
(Refer to settings ZSetting the IP address with address switchesfrom page 133).
IP address 192.168.100.0 is not allowed.
Further information about the setting possibilities of the POWERLINK
®
Controlled Node
refer to „Application Manual“.
Parameters The parameter settings determine the behavior of the POWERLINK
®
Controlled Node in
operation. Parameters are set with the software ProDrive.
1 Start ProDrive
2 Click on „Project Tree“.
3 Communication settings with ProDrive
n Project Tree: Configuration/Fieldbus Slave
(refer also Parameter manual b maXX BM5500, BM5600, BM5700 )
m set Synchronization to „On“
m SYNC time = Fieldbus cycle time = POWERLINK
®
cycle time = 500 µs to 8 ms
This setting is not necessary if using the POWERLINK
®
profile and the POWER-
LINK
®
Managing Node sets a valid value in object 0x1006 „Communication cycle
period“.