Technical Data
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10
61
of 314
3
3.4 Electrical data basic units
3.4.1 Electrical data BM55XX universal units
3.4.1.1 Electrical data BM5X1X universal units
BM5512 BM5513 BM5514-
STX
11)
Rated input power
1)
1.9 kVA
3.3 kVA
5.1 kVA
Rated input current
1)
(I
eff
) 2.8 A 4.8 A 7.3 A
Total harmonic distortion input current (THD)
1)
119 % 110 % 109 %
Max. input current (I
eff
) 5.2 A 9.0 A 20.0 A
Rated DC link voltage
1)
(U
DC
) 540 V
DC
DC link capacitance (internal) 110 F
240 F
330 F
DC link discharging time (internal DC link capacitance) 80 s
175 s
240 s
DC link capacitance (external), permitted Refer to ZFigu
re 34– on page 62
Period between two power up processes
8)
At least 60 s
Output voltage
1)2)
(U
AC
) 3 x 0 V to 3 x 370 V
Output frequency at 4 kHz
10)
0 Hz to 450 Hz
Rated output current
1)4)5)6)
(I
AC
) at 4 kHz
3)
2.5 A 4.5 A 5.5 A
Rated output current
1)4)5)6)
(I
AC
) at 8 kHz
3)
2.5 A 4.5 A 5.0 A
Output peak current
1)4)5)6)
(I
AC
) at 4 kHz
3)
5.0 A 9.0 A 20.0 A
Output peak current
1)4)5)6)
(I
AC
) at 8 kHz
3)
5.0 A 9.0 A 12.0 A
Max. peak current period
7)
60 s 1 s
Connected load DC link terminals
9)
Max. 2.0 kW Max. 3.0 kW
Brake resistor current, permitted (Î) Max. 5.9 A Max. 12.0 A
Brake resistor external 13
0 65
Brake resistor threshold (Û) 780 V
Peak brake resistor power 4.5 kW 5.0 kW 9.4 kW
Permitted continuous brake r
esistor power external 1.0 kW 1.5 kW 3.0 kW
Power loss referring to
power input 33 W 60 W 80 W
Power input referring to control voltage 39 W
Current of the integrated brake control Max. 0.5 A Max. 1.0 A