Electrical data basic units
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
62
of 314
3.4
1)
All rated values refer to a DC link voltage of 540 V, a control voltage of 24 V and an environmental temperature of 40 °C.
2)
The output voltage is a pulsed DC voltage. The operating range refers to the RMS of the fundamental wave.
U
AC
3 0 V to 3
U
DC
2
----------- 10 V


=
without overmodulation of the PWM.
3)
Switching frequency of the inverter (adjustable).
4)
RMS at an environmental temperature of 40 °C.
5)
At rated input supply voltage the device supplies the rated- / maximum output currents. At input voltages above the rated supply voltage
the output currents at constant output power have to be reduced, accordingly.
Output current [%]
Derating of the output current
BM5512, BM5513
Power voltage [V]
Output current [%]
Derating of the output current
BM5514
Power voltage [V]
Figure 33: Derating the output current BM551X universal units
6)
The input current must be reduced between 40 °C and 55 °C, refer to correction factors at changed operating conditions ZEnvironmen-
tal temperatureon page
55.
7)
The possible overload time at this moment is dependent of the device load and the heat sink temperature. The device load is determined
by the overload monitoring of the device.
8)
The specified value is only valid if there is no additional DC link capacitance connected to the DC link terminals. Refer to ZPower on
switching frequency / DC link chargingo
n page 219 and ZFigure 34on page 62.
external DC link capacitance [µF]
Maximum power supply voltage [V]
Figure 34: Maximum external DC link capacitance BM551X un
iversal units
9)
The sum of the transferred mean effective power via the DC link terminals and the transferred mean effective power via the motor ter-
minals may not exceed the specified va
lue continuously.