Electrical data basic units
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
68
of 314
3.4
3.4.1.3 Electrical data BM553X universal units
m Without charging resistor BM553X-XT/BM553X-XG/BM553X-XI
BM5532 BM5533 BM5534 BM5535
Rated input power
1)2)
13.3 kVA 16.8 kVA 26.3 kVA 36.7 kVA
Rated input current
1)2)
(I
eff
) 19.2 A 24.2 A 38.0 A 53.0 A
Total harmonic distortion input current (THD
I
)
1)2)
60 % 54 % 57 % 57 %
Max. input current
2)
(I
eff
) 37.0 A 45.0 A 71.0 A 71.0 A
Rated DC link voltage
1)
(U
DC
) 540 V
DC
DC link capacitance (internal) 940 F 1230 F 1640 F 2000 F
DC link discharging time (internal DC link capacitance) 140 s 210 s 280 s 340 s
DC link capacitance (external), permitted Max. 20 mF
Waiting period between two switching-on operations None
Output voltage
1)3)
(U
AC
) 3 x 0 V to 3 x 370 V
Output frequency at 4 kHz
10)
0 Hz to 450 Hz
Rated output current
1)5)6)7)12)
(I
AC
) at 4 kHz
4)
22.5 A 30.0 A 45.0 A 60.0 A
Rated output current
1)5)6)7)12)
(I
AC
) at 8 kHz
4)
18.0 A 24.0 A 36.0 A
48.0 A
Output peak current
1)5)6)8)12)
(I
AC
) at 4 kHz
4)
45.0 A 60.0 A 90.0 A
90.0 A
Output peak current
1)5)6)8)12)
(I
AC
) at 8 kHz
4)
36.0 A 48.0 A 72.0 A
72.0 A
Max. peak current period
8)
60 s
Power supply DC link terminals
9)
Max. 10.0 kW
Brake resistor current, permitted (Î) Max. 36.0 A Max. 50.0 A
Brake resistor, external 22
16
Brake resistor threshold (Û) 780 V
Brake resistor peak power 29 kW 40 kW
Permitted continuous brake resistor power external 10 kW
Power loss referring to power input 300 W 390 W 600 W 840 W
Power input referring to contr
ol voltage 58 W
Current of the integrated brake control Max. 1.0 A Max. 8.0 A
11)