Electrical data basic units
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
98
of 314
3.4
m With charging resistor BM57XX-XR/BM57XX-XS/BM57XX-XW
BM5766
14)
Rated input power
1)2)
363 kVA
Rated input current
1)2)
(I
eff
) 523 A
Total harmonic distortion input current
1)2)
(THD
I
) 73%
16)
Max. input current
2)
(I
eff
) 455 A
Rated DC link voltage
1)
540 V
DC
17)
DC link capacitance (internal) 10,8 mF
DC link capacitance (external), permitted prohibited
15)
DC link discharging time (internal DC link capacitance) 1840 s
Waiting time between two switching-on operations 55 s
Output voltage
1)3)
(U
AC
) 3 x 0 V to 3 x 370 V
Output frequency at 4 kHz
13)
0 Hz to 450 Hz
Rated output current
1)5)6)7)14)
(I
AC
) at 4 kHz
4)
450 A
Rated output current
1)5)6)7)14)
(I
AC
) at 8 kHz
4)
305 A
Output peak current
1)5)6)8)14)
(I
AC
) at 4 kHz
4)
450 A
Output peak current
1)5)6)8)14)
(I
AC
) at 8 kHz
4)
305 A
Max. peak current period
8)
No limit
Connected load DC link terminals Max. 160 kW
Brake resistor current, permitted (Î) Max. 236 A
Brake resistor, external 3
,33
Brake resistor threshold (Û)
11)
780 V
Brake resistor peak power 183 kW
Permitted continuous brake resistor power external 130 kW
Power loss referring to power input 4800 W
Power loss referring to control voltage 93 W
Power loss of device fan referring to 230 V
AC
9)
174 W
Current of integrated brake control Max. 8.0 A
10)
Cooling air requirement device internal space 200 m
3
/h
Requirement to the water cooling Refer to ZPa
ge 59