Fieldbus communication
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10 Baumüller Nürnberg GmbH
226
of 314
8.4
n Please, observe an EMC-compatible laying of the Ethernet connection cables!
n The following cables were released for use by Baumüller:
Ethernet connection cable;
Further information refer to ZAccessories Ethernet/EtherCAT
®
/VARAN/
POWERLINK
®
.– on page 292.
Commissioning. The following preconditions must be fulfilled before commissioning:
1 BM5500, BM5600, BM5700 with VARAN is installed correctly.
n Ethernet connection cables are wired correctly.
2 The control cabinet is properly locked and all safety devices are operating.
3 The b maXX BM5500, BM5600, BM5700 device is ready-to-use.
4 Create a Lasal-Class2 project using the driver classes for BM5500, BM5600, BM5700
drives for cyclic and service data communication.
5 Start the VARAN control
Address switch By means of the address switches S1 to S4 the IP-address is set
(Refer to settings ZSetting the IP address with address switches– from page 133).
Parameters The parameter settings determine the behavior of the VARAN-Slave in operation. Param-
eters are set with the software ProDrive.
1 Start ProDrive
2 Click on „Project Tree“.
3 Communication settings with ProDrive
n Project Tree: Configuration/Fieldbus Slave
(refer also Parameter manual b maXX BM5500, BM5600, BM5700 )
m Set Synchronization to „On“
m Set Fieldbus cycle time according VARAN cycle time (1 ms, 2 ms, 4 ms or 8 ms)
m Source sync signal = „field bus“