Technical Data
Instruction handbook b maXX BM5500, BM5600, BM5700
Document No.: 5.13008.10
81
of 314
3
m With charging resistor BM556X-XR/BM556X-XS/BM556X-XW
BM5562 BM5563 BM5566
14)
Rated input power
1)2)
184 kVA 227 kVA 351 kVA
Rated input current
1)2)
(I
eff
) 267 A 328 A 506 A
Total harmonic distortion input current
1)2)
(THD
I
) 110 %
17)
112 %
17)
115 %
17)
Max. input current
2)
(I
eff
) 338 A 415 A 628 A
Rated DC link voltage
1)
540 V
DC
18)
DC link capacitance (internal) 10810 F
DC link capacitance (external), permitted Prohibited
16)
DC link discharging time (internal DC link capacitance) 1850 s
Waiting period between two switching-on operations 600 s
Output voltage
1)3)
(U
AC
) 3 x 0 V to 3 x 370 V
Output frequency at 4 kHz
12)
0 Hz to 450 Hz
Rated output current
1)5)6)7)15)
(I
AC
) at 4 kHz
4)
250 A 300 A 350 A
Rated output current
1)5)6)7)15)
(I
AC
) at 8 kHz
4)
200 A 240 A 240 A
Output peak current
1)5)6)8)15)
(I
AC
) at 4 kHz
4)
325 A 390 A 450 A
Output peak current
1)5)6)8)15)
(I
AC
) at 8 kHz
4)
260 A 312 A 312 A
Max. peak current period
8)
60 s
Connected load DC link terminals Max. 160 kW
Brake resistor current, permitted (Î) Max. 230 A Max. 236 A
Brake resistor external 3.
4 3.33
Brake resistor threshold (Û)
11)
780 V
Brake resistor peak power 179 kW 183 kW
Permitted continuous brake r
esistor power external 130 kW
Power loss referring to
power input 3960 W 4800 W
Power loss referring t
o control voltage 93 W
Power loss of the device fan referring to 230 V
AC
9)
174 W
Current of integrated brake control Max. 8.0 A
10)
Cooling air requirement power heatsink 450 m
3
/h
Cooling air requirement device internal space 200 m
3
/h