Swith-on frequeny 7.4T
NOTE
If you count on short mains failures, the reducing of the switching threshold does not make
sense. Instead of that the mains failure reaction delay should be activated via the parameter
486 (AmpNetFailReactDelay). A mains failure effectuates a transition of the controller into sta-
tus 1 and an activation of the precharge circuit without the output of an error message. A mains
error only then is released if the failure time does not exceed the delay time.
Instrution Manual
b maXX
®
BM3400
115
Doument No.: 5.07013.03 from 206