T D App endix D - Tehnial data
BM340x-L1
Input rated power at 8kHz with/without internal chopper re-
sistor
1)
1,0kVA/ 1,7kVA
Input rated current (I
e f f
) with/without internal chopper resis-
tor
4,5A/ 7,4A
Input current max. (I
e f f
) 13,4A
DC link rated voltage
1)
(U
DC
) 310V
DC link capacity (internal) 330µF (V1)/ 940µF (V2)
Output voltage
2)
(U
AC
) 3 x 0V to 3 x 195V
Output frequency 0Hz to 400Hz
Max. Output rated current with internal chopper resistor at
4kHz/ 8kHz/ 16kHz
1)4)5)6)
(I
AC
)
4.3A/ 2.7A/ 1.1A
Max. Output rated current without internal chopper resistor
at 4kHz/ 8kHz/ 16kHz
1)4)5)6)
(I
AC
)
7.0A/ 4.5A/ 2.7A
Max. Output peak c urrent at 4kHz/ 8kHz/ 16kHz
1)4)5)7)
(I
AC
) 8.1A/ 8.1A/ 8.1A
Max. Peak current time with internal chopper resistor at 4kHz/
8kHz /16kHz
7)
2,3s/ 1,2s/ 0,44s
Max. Peak current time without internal chopper resistor at
4kHz/ 8kHz /16kHz
7)
60s/ 24s/ 4,1s
Chopper resistor current, valid (I)
8)
7A
Chopper resistor internal, (optional) (P) P
cont .
= 30W
Chopper resistor internal (optional) (R) 100
Chopper resistor external (R) > 60
Chopper start-up voltage (U) 400V
Chopper shutdown voltage (U) 380V
Chopper peak power 2.8kW
Chopper nominal power 1.0kW
Power loss referring to mains voltage
9)
max. 100W
Power loss referring to control voltage
10)
max. 30W
180