Accessories and Spare Parts
Instruction handbook b maXX BM4400, BM4600, BM4700
Document No.: 5.12008.07
301
of 358
11
Power choke
type code
Figure 107: Type code power choke
The listed chokes are specified for the operation at 400 V /50 Hz or 480 V / 60 Hz.
At a power supply voltage of 400 V and a frequency of 50 Hz at rated current the chokes
have a short-circuit voltage > 3% of the power supply voltage.
UL approval
The chokes are design-tested in accordance with UL (e.g. UL1561) and signified by the
ú“ symbol.
B K X - XXXX / XXX - XXX
Baumüller
Commutation choke
No. of phases
1: Single phase choke
3: Three phase choke
Rated AC current I
eff
Development status/design
001: Connection copper bar, overload factor 1,1
002: Connection terminal, overload factor 1,1
101: Connection copper bar, overload factor 2
102: Connection terminal, overload factor 2
DC set value
- Single phase choke: 1,0 x I
eff
- Three phase choke: 1,22 x I
eff
I
rated AC
Induc-
tance
Type code Part No.
type -101,
connection
copper bar
Part No.
type -102,
connection
terminal
For devices
24 A 1,22 mH BK3-0024/0029 - 456715 BM4426
53 A 0,55 mH BK3-0053/0070 - 456717 BM4632
82 A 0,36 mH BK3-0082/0100 - 456718 BM4641
95 A 0,31 mH BK3-0095/0116 - 456720 BM4642
125 A 0,23 mH BK3-0125/0153 - 456722 BM4650
160 A 0,18 mH BK3-0160/0196 - 456723 BM4651
190 A 0,15 mH BK3-0190/0232 456725 - BM4652
240 A 0,12 mH BK3-0240/0294 456728 - BM4661
285 A 0,10 mH BK3-0285/0350 456729 - BM4662