Chapter 3 Parameters
Mini-Switch LB 471
17
Chapter 3. Parameters
3.1 Standard Mode / Professional Mode
The operation mode is set in code 04. The following table explains
the differences between standard and professional mode.
Standard mode
Professional mode
Operation
Simple
Access to all addition-
al functions. See pa-
rameter list on page
19.
Factory setting
Standard mode is preset by the manufacturer.
Parameters
Only the major para-
meters are available.
All parameters are
available.
Calibration
Calibration is per-
formed automatically
by reading in the emp-
ty count rate.
First, all parameters
have to be set. You
can start a calibration
only in code 36.
Behavior of
auto / manual
parameters
during calibra-
tion
These parameters are
set to automatic to
speed up the getting
started process.
These parameters are
not affected during
calibration.
Calibration
error
Possible calibration
errors are indicated as
soon as you start
empty calibration.
Possible calibration
errors are indicated
only after you have
started calibration
with code 36.
Change
between pro-
fessional and
standard mode
All settings are re-
tained. The special
parameters for the
professional mode are
hidden.
All settings are re-
tained. The special
parameters for the
professional mode can
be displayed in addi-
tion.
Table 1:
Operation modes
Standard / Professional