Chapter 3 Functional Safety
Mini-Switch LB 471
3.5 Getting Started
The conditions at the facility affect the safety of the measuring
system. Therefore, the mounting and installation instructions in
the User’s Manual have to be observed. In particular, the correct
setting of the parameters has to be ensured. For more information
on the parameters and on getting started, please refer to the Us-
er’s Manual LB 471 ID No. 39505BA2.
The device may be operated as safety-relevant only in the profes-
sional mode.
1
Reset
Keep Clear button pushed and turn the power supply on.
The device is reset to factory setting.
Basic parameter setting
Set parameters according to the following parameter list.
The order in which the parameters have to be set is shown
in the last column.
Fields that are not numbered in this column are display
parameters or parameters that remain on factory setting.
If the Value column includes data, then you have to enter
this data exactly.
If no data has been entered in the Value column but a
number has been entered in the last column, then the
value of the parameter has to be adapted to the given
measurement situation. However, the value has to be
adapted only if this is required by the measurement situa-
tion.