120 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
first. When Perimeter Relay (Section Perimeter Relay, page 178) is set to Yes, the A# Fail to
Close prompt becomes A# Perimeter Relay.
A# Force Armed
This relay activates when this area is Force Armed. It remains active until the area disarms or
the control panel resets.
A# Watch Mode
This relay activates when a Controlled point programmed for P## Watch Point is faulted in
the specified area while the area is in Watch Mode and the point is not armed. It remains
active for 2 sec after each point is faulted.
A# Area Armed
This relay activates when the specified area becomes Master Armed. The exit delay must
expire before the relay activates. The relay remains active until the area disarms. It does not
deactivate during the entry delay time.
If multiple areas use the same relay, the relay activates when all areas are armed. It
deactivates when the first area disarms.
The A# Area Armed relay function can provide visual feedback at a key switch station. Attach
a LED to the output of a D8129 Module programmed for this function.
A# Area Fault
Activates whenever a controlled (P## Type 1, 2, 3 only) Perimeter or Interior point is faulted.
The relay remains active until all Perimeter and Interior points in the area are normal.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
NOTICE!
If Force Bypassing is required during Perimeter Arming, this relay does not activate.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
NOTICE!
Keyswitch area armed status with LEDs: Use a D8129 Module and connect an LED to indicate
that the area is not ready to arm.