152 en | Points D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
CMD7 Point Index
This entry selects one of the 31 P## Index codes that define how the control panel reacts
when a COMMAND 7 is initiated.
CMD7 Relay
This entry selects a relay (73 to 80 for the D9412GV4 or 9 to 16 for the D7412GV4 and
D7212GV4) when COMMAND 7 is initiated (refer to the Section P### Relay Codes/Relays,
page 148 for relay number association).
CMD7 Point Text
Enter alphabetic characters A to Z in capital letters.
Enter up to sixteen characters of text to describe the point. This point text appears at keypads
(if the point is programmed as visible) and sent to the D6500 or D6600 when transmitting in
Modem IIIa
2
format (if it is a reporting point).
CMD9 Point Index
This entry selects one of the 31 P## Index codes that define how the control panel reacts
when a COMMAND 9 is initiated.
Default: 31
Selection: 0 to 31
NOTICE!
The point index code used for COMMAND 7 must not be used for any other points on the
system.
NOTICE!
If the point index for COMMAND 7 has Fire points programmed as Yes, this causes access
control doors to unlock if Fire Unlock is also programmed as Yes.
Default: 0
Selection: 0 to 8
NOTICE!
COMMAND 7 does not activate the Summary Fire Alarm relay.
Default: COMMAND 7
Selection: Up to sixteen alphanumeric characters
Default: 31
Selection: 0 to 31
NOTICE!
The point index code used for COMMAND 7 and COMMAND 9 must not be used for any other
points on the system.
NOTICE!
If the point index for COMMAND 9 has Fire points programmed as Yes, this causes access
control doors to unlock if Fire Unlock is also programmed as Yes.