EasyManua.ls Logo

Bosch D7412GV4 - Page 37

Bosch D7412GV4
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 37
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Table 3.10 Diagnostic Reports
Relay Reports
Selecting Yes enables sending a report when the event occurs.
Report Selections Report Description
R# SDI Device Fail
1
Yes, No SDI device failure
R# SDI Device
Restoral
Yes, No Restoral of SDI device failure
R# Watchdog Reset Yes, No Watchdog Reset Event
R# Parameter
Checksum Fail
Yes, No Parameter checksum failure
R# Reboot Yes, No Reboot Event
R# Phone Line Fail
1
Yes, No Failure of phone line
R# Phone Line
Restoral
Yes, No Restoral of phone line afterfailure
R# AC Fail
1
,
2
Yes, No Failure of AC power to control panel
R# AC Restoral
2
Yes, No Restoral of AC power to control panel after failure
R# Batt Missing
1
,
2
Yes, No Battery Missing Detection Event
R# Battery Low
1
,
2
Yes, No Low battery power
R# Battery Restoral
2
Yes, No Restoral of battery power to control panel after Missing
or Low Event
R# Rt Comm Fail
1
,
3
Yes, No Failure to send report to specific route
R# Rt Comm Restoral Yes, No Restoral of communication to specific route after a
failure
R# Rt Comm Restoral Yes, No Restoral of communication to specific route after a
failure
R# Checksum Fail Yes, No Checksum Fail Event
R# Network Fail
4
Yes, No Failure of network
R# Network Restoral
4
Yes, No Restoral of network
R# Network
Condition
4
Yes, No Condition of network
R# RF Interference Yes, No RF receiver interference
R# RF Interference
Restoration
Yes, No RF receiver communication restored
R# Equipment Fail Yes, No Trouble on SDI2 device
R# Equipment Fail
Restoration
Yes, No Restoration of trouble on SDI2 device
1
This event is included in the Expanded Test Report when an off normal condition exists.
2
To meet UL 864 requirements for Central Station and Remote Station applications (D9412GV4 and
D7412GV4), enable AC Fail, Battery Missing, Low Battery, Battery Restoral, and AC Restoral reports.
3
This event covers Comm Fail Route Group and Comm Fail Phone. If enabled, both events are sent; if
disabled, neither event is sent.
4
This event is reserved for future use.
NOTICE!
Enable Rt Comm Fail and Rt Comm Restore in only one route group.
Report Selections Report Description
R# Sensor Reset Yes, No Sensor Reset Event
R# Relay Set Yes, No Relay Set Event
R# Relay Reset Yes, No Relay Reset Event